POWER SUPPLY CP-C 24/20.0 (ABB)
Giá: Liên hệ
Technical
- Function:
- Switch mode power supply
- Number of Phases:
- 1
- Rated Input Voltage (UIN):
- 100 ... 240 V AC
90 ... 300 V DC
- Input Voltage (Uin):
- 85 ... 264 V AC
90 ... 300 V DC
- Typical Input Current:
- (115 V AC) 4.6 A
(230 V AC) 2.3 A
- Hold-up Time:
- (230 V AC) min. 40 ms
- Rated Frequency (f):
- 50 Hz
60 Hz
- Rated Frequency Limits:
- 45 ... 65 Hz
- Characteristic of Output:
- U/I characteristic curve with power reserve
- Rated Output Power:
- 480 W
- Output Power:
- 480 W
- Rated Output Voltage:
- 24 V DC
- Output Voltage (Uout):
- 24 V DC
- Rated Output Current:
- -25 °C ... +40 °C 26 A
-25 °C ... +60 °C 20 A
- Output Current:
- 20 A
- Output Current Maximum (Iout):
- 26 A
- Rated Impulse Withstand Voltage (Uimp):
- Input Circuit / Output Circuit 4 kV
Input Circuit / PE 4 kV
Input Circuit / Relay Contact 4 kV
Output Circuit / PE 0.5 kV
Output Circuit 0.5 kV
- Rated Insulation Voltage (Ui):
- Input Circuit / Output Circuit 300 V
Input Circuit / PE 300 V
Input Circuit / Relay Contact 300 V
Output Circuit / PE 50 V
- Degree of Protection:
- Housing IP20
Terminals IP20
- Pollution Degree:
- 2
- Connecting Capacity Input Circuit:
- Flexible with Ferrule 0.5 ... 2.5 mm²
Flexible 0.5 ... 2.5 mm²
Rigid 0.5 ... 4 mm²
- Connecting Capacity Output Circuit:
- Flexible with Ferrule 2.5 ... 10 mm²
Flexible 2.5 ... 10 mm²
Rigid 2.5 ... 16 mm²
- Tightening Torque:
- Auxiliary Circuit 0.5 N·m
Input Circuit 0.5 N·m
Output Circuit 1.2 N·m
- Wire Stripping Length:
- Auxiliary Circuit 8 mm
Input Circuit 8 mm
Output Circuit 10 mm
- Recommended Screw Driver:
- Input Circuit / Output Circuit PH1
Input Circuit / Output Circuit 0.8 x 4
- Minimum Mounting Distance:
- Electrical Conductive Board, Horizontal 25 mm
Electrical Conductive Board, Vertical 25 mm
Other Device Same Type, Horizontal 25 mm
Other Device Same Type, Vertical 25 mm
- Mounting Position:
- Position 1, 7
- Mounting on DIN Rail:
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- Standards:
- EN 50581
IEC/EN 60950-1
IEC/EN 61204
IEC/EN 61000-6-2
IEC/EN 61000-6-3
UL 508
CAN/CSA C22.2 No.107.1
Environmental
- Ambient Air Temperature:
- Operation -25 ... +70 °C
Storage -40 ... +85 °C
- Resistance to Vibrations acc. to IEC 60068-2-6:
- 10-58 Hz, ±0.15 mm; 58-150 Hz, 2g, 10 sweep cycles each axis
- Resistance to Shock acc. to IEC 60068-2-27:
- 30g / 3 shocks / 6 ms
- Resistance to Damp Heat acc. to IEC 60068-2-30:
- Test Db: 55°C, 2 cycles
- RoHS Status:
- Following EU Directive 2011/65/EU