CB T2S 160 32A
Giá: Liên hệ
- Circuit Breaker Type to be Associated:
- Motor protection
- Electrical Durability:
- 120 cycles per hour
8000 cycle
- Mechanical Durability:
- Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
- Number of Poles:
- 3
- Opening Time:
- CB with SOR 15 ms
CB with UVR 15 ms
- Power Loss:
- at Rated Operating Conditions per Pole 2.57 W
- Product Main Type:
- SACE Tmax XT
- Product Name:
- Moulded Case Circuit Breaker
- Product Type:
- CB
- Rated Current (In):
- 32 A
- Rated Frequency (f):
- 50 / 60 Hz
- Rated Voltage (Ur):
- 690 V
- Rated Impulse Withstand Voltage (Uimp):
- 8 kV
- Rated Instantaneous Short-Circuit Current Setting (Ii):
- 448 A
- Rated Insulation Voltage (Ui):
- 1000 V
- Rated Operational Voltage:
- 690 V AC
500 V DC
- Rated Service Short-Circuit Breaking Capacity (Ics):
- (220 V AC) 85 kA
(220 V AC) 85 kA
(380 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 36 kA
(690 V AC) 12 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu):
- (220 V AC) 85 kA
(230 V AC) 85 kA
(380 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 36 kA
(690 V AC) 12 kA
(250 V DC) 2 Poles in Series 50 kA
(500 V DC) 3 Poles in Series 50 kA
- Rated Uninterrupted Current (Iu):
- 160 A
- Release Type:
- M
- Standards:
- IEC
- Sub-type:
- XT2
- Terminal Connection Type:
- Fixed Circuit-Breakers
Front
- Version:
- F